SITE MANAGEMENT • GENERAL SETUP
TECHNICAL SUPPORT 978-486-0086 • support@burk.com • www.burk.com
STATUS INPUTS
The digital inputs, or status inputs, on an I/O unit
are programmed in the Status Input Table. To
open the Input Table window, double-click on the
Status icon in the General Setup window.
The following areas can be edited through this window:
Type
Depending on the output method used by the equipment being
monitored, either Pull-Up or Pull-Down must be selected.
Pull-Up should be selected if monitored equipment provides a
contact closure to indicate a Low state. Pull-Down should be
selected if monitored equipment provides a DC voltage to indicate
a High state.
Low Name
Label shown on monitoring software when status condition is in a
Low or False state.
High Name
Label shown on monitoring software when status condition is in a
High or True state.